B/128, GIDC Electronics Estate, Sector-25,Gandhinagar - 382025, Gujarat, India.
Features | |
---|---|
Faults | input Phase reverse, Battery reverse polarity, Cabinet Over temp, Door interlock, All Grid faults are built in - OV, UV, UF, OF Safe turnoff under Output Short circuit. |
Special feature |
Built In DC & AC Precharge, Control Battery Charging in OFF grid Mode, Smart Grid Tie Power saving Mode, SOC based charging Mode, Black Start in off Grid Mode |
Technology | With Built-in Isolation Transformer, 4-quadrant operation |
Wide DC Input range |
200-1500 VDC, Derating: 1350-1500 VDC |
Standards Compliance |
IEEE 1547, UL 1741 SA REV3 |
Input Specifications | |
---|---|
DC Voltage Range 4 | Nominal : 200 - 1000 VDC Optional > 1000 VDC |
Max Countinuous DC Current/Voltage Rippel |
715 A / < 1% |
Maximum /Minimum DC voltage for full power |
900/ 350 VDC |
Power range | 140KVA@200V&@1000V/ 175KVA@250V/ 210KVA@300V/ 250KVA@350 V DC |
Environmental Specification | |
Operating Temp 3 | -25 to 60 °C |
Cooling | Forced Air Cooled |
Related Max. Elevation |
1,000 Meters Full Power Up to 3,000 meters with Derating |
Enclosure 2 | RAL 9005, IP 54/ IP 34 |
Dimensions (HXWXD) | 1796 X 942 X 815 mm ( ± 5 mm) |
Approximate Weight in kg |
1200 |
User Interface | |
Remote Monitoring & Communication |
Modbus TCP with Automated Alerts |
Grid Connections | |
AC Line Voltage | 480 / 415 VAC (+15%, -15%), 3-Ph |
AC Line Frequency | 60 / 50 Hz (+ / - 1%) Settable |
Continuous AC Current |
301 / 348 A RMS |
Overload AC Current | 320 / 366 A RMS |
Continuous AC Power | 250 KW |
Overload AC Power | 300 KW |
Power Factor | +1.0 to -1.0 |
Current Harmonics | IEEE 1547 Compliant, <3% TDD |
Peak Efficiency | 97.80% |
“All Product Names, Logos, and Brands are Property of their respective Owners. All Company, Product and Service names used in this catalog are for identification purposes only. Use of these Names, Logos and brands does not imply endorsement.”
Terms& Conditions of usage
The data contained in this product data sheet is exclusively intended for technically trained staff. Technical departments will have to evaluate the suitability of the product for the intended application and the completeness of the product data with respect to such application.
This product data sheet is describing the characteristics of this product for which a warranty is granted. Any such warranty is granted exclusively pursuant the terms and conditions of the supply agreement. There will be no guarantee of any kind for the product and its characteristics.
Should you require product information in excess of the data given in this product data sheet or which concerns the specific application of our product, please contact the sales office, which is responsible for you (see www.paramvirpower.com). For those that are specifically interested we may provide application notes.
Due to technical requirements our product may contain dangerous substances. For information on the types in question please contact the sales office, which is responsible for you.
If and to the extent necessary, please forward equivalent notices to your customers.
Changes of this product data sheet are reserved.
Safety Instructions
Prior to installation and operation, all safety notices and warnings and all warning signs attached to the equipment have to be carefully read. Make sure that all warning signs remain in a legible condition and that missing or damaged signs are replaced.
Even for customer-specific products, conclusive validation of the component in the circuit can only be carried out by the customer.